The question
A furnace or heat pump is sized from the heating load: how many Btu per hour the house loses on a design-cold night. Air sealing and insulation change that number. For an ordinary older house in Erie, how much does a closed-cell spray foam retrofit change it, and what does that mean for the equipment?
The house and the inputs
A two-story colonial, 25 × 40 feet, 2,000 square feet above a full basement. The retrofit is the work we do most in older homes: seal the attic floor and top it up, and spray closed-cell foam on the rim joists. The walls and windows stay as they are.
| Input | Before | After | Where it comes from |
|---|---|---|---|
| Design temperatures | 70°F in, 11°F out | same | Erie's 99% heating design temperature (ASHRAE 2025); Manual J uses the 99% value |
| Walls, 1,870 sq ft net | 2×4, R-11 fiberglass, U-0.093 | unchanged | Cavity and stud paths, 25% framing |
| Windows and doors | 300 sq ft at U-0.50, 40 sq ft at U-0.40 | unchanged | Older double-pane windows |
| Attic floor, 1,000 sq ft | About R-19 left, U-0.048 | Bypasses sealed with closed-cell, topped up to R-49, U-0.020 | |
| Rim joists, about 100 sq ft | Bare 2×10 and sheathing, U-0.26 | 3 in. closed-cell, U-0.040 | About R-21 for the 3 in. of foam (one HFO product lists R-14 at 2 in. and R-26 at 3.5 in.) |
| Air leakage | 10 ACH50 | 6 ACH50 (40% less) | LBNL's ResDB equates 10 ACH50 with a normalized leakage of 0.55; detached U.S. houses average about 0.61, and older ones leak more. See the range below |
Method
Each surface loses heat at its U-factor times its area times the temperature difference (59°F). Air leakage is converted from the blower-door number to a design-condition airflow (ACH50 × 24,000 cubic feet, the basement included, ÷ 60 ÷ 15) and costs 1.08 × cfm × 59°F. That is the core of an ACCA Manual J heating calculation. Manual J software adds the basement, duct losses and its own leakage method; those add to both columns, so they are left out to keep the comparison clean.

Results
| Part of the heating load | Before | After |
|---|---|---|
| Walls (unchanged) | 10,250 Btu/h | 10,250 Btu/h |
| Windows and doors (unchanged) | 9,790 Btu/h | 9,790 Btu/h |
| Attic floor | 2,850 Btu/h | 1,160 Btu/h |
| Rim joists | 1,550 Btu/h | 240 Btu/h |
| Air leakage | 16,990 Btu/h | 10,200 Btu/h |
| Total | 41,430 Btu/h | 31,640 Btu/h |
Air leakage was the biggest single part of the load, about 41% of it, and it is where closed-cell foam does most of its work: at the rim joists and the attic floor, two of the places older houses leak.
How much the leakage drops decides the result:
| Air leakage after | Cut | Heating load after | Load reduction |
|---|---|---|---|
| 7.5 ACH50 | 25% (ENERGY STAR's modeling assumption) | 34,190 Btu/h | 17% |
| 6 ACH50 | 40% | 31,640 Btu/h | 24% |
| 5 ACH50 | 50% | 29,940 Btu/h | 28% |
A blower-door test before and after settles which row a real house lands in.
What it means for the equipment
- Heat pump. NEEP's cold-climate guide says to match the heat pump's capacity at the design temperature to 100 to 115% of the heating load (the DOE's guidance: size to the design heating load, with slight oversizing acceptable). Before the retrofit that is about 41,000 to 48,000 Btu/h at 11°F; after, about 32,000 to 36,000. The difference is roughly 10,000 Btu/h, close to one nominal ton, usually one equipment size.
- Furnace. ENERGY STAR's design rules allow a heating-only furnace of 100 to 140% of the load. Before, that tops out near 58,000 Btu/h of output; after, near 44,000.
- Cooling. The same attic and air-leakage changes cut the cooling load too, but this estimate doesn't calculate it. Erie County is heating-dominated (RESNET lists a heating-to-cooling degree-day ratio of 2.9), so the heating load sets a heat pump's size.
- Money. The smaller unit costs less up front, and a unit matched to its load runs longer, steadier cycles. In This Old House's 2026 national averages for central air, a 4-ton system averages $13,136 and a 3-ton system $8,654.
What the numbers do and don't say
- It is a worked estimate, not a Manual J report. A real calculation adds the basement, ducts, the house's measured leakage and room-by-room loads. The difference between the two columns is the useful part.
- The walls set a floor. With the walls and windows unchanged, they are 63% of the load after the retrofit. When walls are open, in a gut renovation or new construction, closed-cell in the walls takes the load down further.
- Do the envelope first. NEEP's heat pump guide says it directly: "Planned weatherization work should be done first if possible, to reduce HVAC size and cost." Then size the new equipment to the house as it is.
Savings vary. Find out why in the seller's fact sheet on R-values. Higher R-values mean greater insulating power.
Assumptions: steady state at the 99% design temperature; series-parallel wall U-factor with interior and exterior air films, siding R-0.6, sheathing R-0.5, drywall R-0.45, studs at R-1.25 per inch; attic floor with air films and drywall; design infiltration from ACH50 ÷ 15; no internal or solar gains in the heating load, as Manual J does.
Sources
- HVAC design temperature limits by county, RESNET ANSI 301 Appendix A (2019)
- HEATLOK HFO High Lift Technical Data Sheet, Huntsman Building Solutions
- Erie International Airport (725260) design conditions, ASHRAE Handbook 2025 values, climate.onebuilding.org
- Residential Diagnostics Database (ResDB), Lawrence Berkeley National Laboratory
- Chan, Joh and Sherman, Analysis of air leakage measurements of US houses, LBNL (2012)
- ENERGY STAR: Methodology for estimated energy savings from air sealing and insulating
- ENERGY STAR National HVAC Design Supplement, Rev. 14 (2025)
- Guide to Sizing & Selecting Air-Source Heat Pumps in Cold Climates, NEEP
- Cold Climate Heat Pump Sizing and Selection, DOE Building America Solution Center
- Air conditioner costs, This Old House (October 2026)